Loss prevention: Infrared Thermography on electrical panels,

distribution system, substation

 

 

The IR thermography inspection on electrical systems,

allow the detection and evaluation of excessive or unbalanced loads,

poor connections, oxidation and other faults invisible to the naked eye.

 

The thermography technique grants corrective and predictive maintenance

through the remote identification and measurement

of the heat produced by the electric system’s components.

 

The thermographic analysis is a non-conctact and non-destructive inspection technique, UNI EN 9712 (473).

It is carried out on the electrical system while it is full-load operating without interrupting the current supply.

All the measurements are performed by a secure distance

which ensure to avoid the threat of electrical work under voltage.

 

Società Ingegneri Verificatori SIV srl

our Company, SIV srl, is an “inspection body type A” according to EN 17020, third-party and independent,

authorized by the Italian Ministry of Economic Development to inspect electrical installations,
and the operators are experienced and certified EN ISO 9712 electrical II° level, by RINA.

 

 

electrical panel thermography

 

Our company SIV srl "SOCIETA' INGEGNERI VERIFICATORI"

work throughout Europe and over

 

SIV srl is an “inspection body type A” according to EN 17020, third-party and independent,

authorized by the Italian Ministry of Economic Development to inspect electrical installations,
and the operators are experienced and certified EN ISO 9712 electrical II° level, by RINA.

Our thermal cameras measure a temperature range between -40°C (=233°K) and +350°C (=623°K)

 

We perform Thermography on medium-voltage electrical systems (15kV - 20kV)

and high-voltage, 132kV substations.

 

Quotation for an electrical systems thermography:

please contact our Technical Manager Dott. Eng. Manuel Boarini for a quote, at:

email: siv@siv.bo.it   mobile phone: +39 339 5674473

 

SIV srl  via Boldrini 18, Bologna, 40121, Italy
email: siv@siv.bo.it       tel: +39 051 379050     p.iva 02344271206

 

 

 

 battery pack thermography

Infrared inspection: forklift’s charging battery thermography

 

 

 

electrical panel thermography    Infrared inspection Thermography on electrical panel

 

Infrared inspection Thermography on electrical panel    Infrared inspection Thermography on electrical panel

 

Infrared inspection Thermography on electrical panel    Infrared inspection Thermography on electrical panel

 

 Infrared inspection Thermography on electrical panel    Infrared inspection Thermography on electrical panel

 

Infrared inspection Thermography on electrical panel

 

 

 

 

Infrared inspection Thermography on high voltage substation 132kV     Infrared inspection Thermography on high voltage substation 132kV

 

132kV high-voltage Substation thermography

 

Infrared inspection Thermography on high voltage substation 132kV      Infrared inspection Thermography on high voltage substation 132kV

 

132kV high-voltage Substation thermography

 

Infrared inspection Thermography on high voltage substation 132kV     Infrared inspection Thermography on high voltage substation 132kV

132kV Substation thermography

 

 

Infrared inspection Thermography on high voltage substation 132kV     Infrared inspection Thermography on high voltage substation 132kV

  

132kV Substation thermography

 

 

Infrared inspection Thermography on high voltage substation 132kV

 

132kV high-voltage Substation thermography

 

 

 

Infrared inspection Thermography on 20kV transformer   Infrared inspection Thermography on 20kV transformer

Infrared inspection: medium-voltage 20kV transformer Thermography

 

 

 

Infrared inspection Thermography on 20kV transformer   Infrared inspection Thermography on 20kV transformer

Infrared inspection: medium-voltage 20kV transformer Thermography

 

 

Infrared inspection Thermography on 20kV transformer

 

medium Voltage 20kV/400V Transformer Termography

 

 

_______________________________________

 

 

 

 


 

 

 

 

   

 

Sample report:

ELECTRICAL SYSTEMS’ THERMOGRAPHY

 

  

Place and date    

 


 

Report sample

 

SIV srl, “SOCIETA’ INGEGNERI VERIFICATORI” is an “inspection body type A” according to UNI EN 17020, third-party and independent, authorized by the Italian Ministry of Economic Development to inspect electrical installations

The operators are certified RINA II° level UNI EN ISO 9712

Infrared thermographic check of the electrical systems allows the client to negotiate a reduction in the fire insurance premium. Furthermore, regarding the company own prevention and maintenance annual program, checking the electrical systems with IR allows the client to keep under control:

·       the materials’ deterioration

·       the danger of surges that can cause fire risk

·       the tightening and oxidation of the power contacts with consequent risk of dangerous overheating and plant’s operating faults;

·       the risk of production’s shutdowns, plant stoppage and electric black out;

·       the predictive maintenance of the equipements and installations

 

 

 

The check operations

 

- Visual inspection of the electrical system.

- Instrumental measurement of temperature by infrared radiation on transformers, power terminal blocks, electrical switchboards, circuit breakers and switches, critical equipment

- Measures with amperometric clamp, electrical phases analyzer and other instruments

- Acquisition of visible and infrared images of the points where anomaly heating and/or temperature changing are detected

- The instrumental tests are carried out on plants under electrical voltage in normal operating conditions, therefore they do not require the interruption of electrical supply

- Report’s draft

- The customer should provide the assistance of a qualified electrician during the check activities


 

 

Report sample

Ref. Electric switchboard…

infrared inspection on panel

 

Site: xxxxxxxx

Assistant: xxxxxxxx

inspection body

SIV srl   UNI EN 17020 


Operators
Eng. Boarini     II° level ISO EN 9712
 

file name: IR_0385.jpg

Date and time of data collection: 2014:11:26 4:21:37PM

Size, kb: 354

Distance, cm: 100/100
Air temperature: 20°C
Emissivity: …
Reflexed Temperature:…
Oriz. Res. Px: …
Vert. Res. Ps: …
Softw: IRSDK Ver. 1.1.  EXIF2HTM Ver 1.07
Rev.: MB 1.011-27


 

 Report sample

Reference regulations and standards

Check operations

-        Visual inspection of the electrical system

-        Instrumental measurement of temperature by infrared radiation on transformers, power terminal blocks, electrical switchboards, circuit breakers and switches, critical equipment. Measurement are made on equipements under voltage.

-       Acquisition of visible and infrared images of the points where anomaly heating and/or temperature changing are detected

-       Report’s draft


 

 Test instrumentation

-         Report sample

 

Test conditions and method

Report sample

Method: comparative measurement of electrical phases

Report sample

Overloaded temperature measurement is taken in two ways: directly in the place where the damage occurred or throw the heat radiation from the broken device’s external surface

 

Report sample

Load conditions: standard operation, constant load

Additional information from amperometric clamp

IR observation: from different perspective angles

Noise factors (wind, rain, distance): NO

Operative factors:

thermocamera setting: YES

Standard emissivity:

Ref. temperature: 20°C

Items’ distance : 0,1-1m

 

Results evaluation

 Report sample

Investigations, the heating:

·        It is not a reflex

·         the surface it is not glossy

·         it is not a natural hot spot

·         it is not solar heating

·         it is not induction heating (caused by magnetic effects)

·         it is not a time varying load

 

Classificazione della possibile causa della sovratemperatura (difetto):
Over-heating causes’ classification:

o      loosen electric conctact

o      oxidation

o      junction made of different metals

o      unbalanced load

o      bundled cables, cooling shortage

o      Load back-flow

 

Other possible causes of overheating

·       undersized equipements

·       lack of air circulation

 


 

 

Intervention criteria recommended

 Report sample

Inspection results

Report sample

Thermographic results

 Report sample

Conclusions: except for the above statements, there are no significant thermal anomalies on the electrical plant

 

Monitoring

To ensure greater efficiency of the maintenance cycle and lower risk of the plant, it is recommended the maintenance and the monitoring of the components indicated by the annual thermographic inquiries

 

 

                                                                                         

Attachments: inspection reports with IR photos and technical feedbacks

 

 

 

Electric plant thermography

electric switchboards, medium voltage electric transformer, 132kV high voltage substation

 

Società Ingegneri Verificatori SIV srl

“inspection body type A” according to UNI EN 17020, third-party and indipendent, authorized by the Italian Ministry of Economic Development (“Ministero dello Sviluppo Economico”)

Our company works throughout Italy and Europe

 

Our operators are certified RINA II°level EN ISO 9712

 

 

Our thermal cameras measure a temperature range between -40°C (=233°K) and +350°C (=623°K)

 

 